Pelican Z eAir E

SKU: 10023784
EAN: 6415879356914
Delivery time: 2 weeks, will be confirmed separately

Ventilation unit with heat recovery and electrical after heater. The unit is equipped with Enervent eAir control.

Available

The Enervent Pelican Z unit is best suited for large detached houses or public spaces, like offices. Pelican Z is the smallest unit in our range that can be fitted with a built-in extract air heat pump (HP). All heating and cooling coils, as well as the heat pump unit, are built-in to the unit.

General information

Air volume flow @ 100 Pa: 50–650 m³/h
Pressure difference: 25–100 Pa
Leakage external: < 5% (test pressure 300Pa)
Leakage internal: < 5% (test pressure 300Pa)
Duct size: Ø 200 mm
Weight: 125 kg
Standard filters, 2 x bag filter: ISO ePM1 60%/ISO Coarse 80% (F7/M5)
IP class: IP44 (external control IP20)
Water heating coil connections: Intake/return 15 mm
Water cooling coil connections: Intake/return 15 mm
Evaporator connections: Intake ½”, return 15 mm
Condense connection: ¼” internal thread
Nominal voltage: 230 V
Nominal current: Motors 2.4 A total, electrical after heating 8.7 A

Fans

Supply and exhaust air fan type: Ebm-Papst
Supply and exhaust air motor type: R3G190-RD45-17
Nominal voltage: 230 V (AC)
Type of fan blade: Radial backward
Nominal power: 169 W, 1.35 A, 50 Hz
Fan control eAir control: Stepless (supply and exhaust running separately)

Heat exchanger

Heat exchanger type: Rotating heat exchanger
Material: Aluminium
Heat exchanger surface: 70 m²
Heat exchanger dimensions: 450 x 200 (60 μ)
Heat exchanger motor: 6 W
Ventilation unit annual temperature efficiency (EN 13141-7:2010): 77,7 %
Supply air annual heat recovery efficiency* (EN 16798-3:2017): 91,3 %
Extract air annual heat recovery efficiency* (D5:2012): 77,5 %
* supply air +18°C, extract air +21°C, exhaust air temperature limit -7°C

Other information

Material inside cover: Steel sheet, zinc coated
Material outside cover: Steel sheet, zinc coated, powder painted
Sound level in supply air duct at fan speeds 20, 40, 60, 80 and 100% LWA: -, 60, 67, 74, 78
LPA, dB(A), 10 m²: sound absorption: -, 35, 40, 45, 48
Standard electric after heater efficiency: 2 000 W
Positioning of cooling (CG) coil: Built-in

Do you need help choosing the right product?

We will gladly help you. Contact our customer service phone +358 9 4255 0305 (week days 8-16 UTC+2), e-mail: enervent@enervent.com or technical support phone +358 9 4255 0303 (week days 8-16 UTC+2), e-mail: service@enervent.com.