LTR-7 Z eAir E

SKU: 10023619
EAN: 6438269033011
Delivery time: 2 weeks, will be confirmed separately

Ventilation unit with heat recovery and electrical after heater. The unit is equipped with Enervent eAir control.

Available

The Enervent LTR-7 Z unit is best suited for large detached houses and public spaces, such as schools and kinder gardens.
The LTR-series units are designed for installation in the roof, in the attic, in a false ceiling or in a technical space. The horizontal installation often saves a lot of space. LTR-series units are well insulated and can be installed in cold places. The unit needs additional insulation if the temperature around it drops below -10°C. The simple but ingenious structure
and the low pressure drop of the unit ensure an inexpensive and safe operation.

Enervent LTR-7 Z is a ‘non-residential ventilation unit’ (NRVU) according to the EU Commission Regulation No 1253/2014. Ventilation units with maximum flow rate between 250 and 1 000 m3/h which the manufacturer has not declared intended as being exclusively for a residential ventilation application are called non-residential. Non-residential ventilation units (NRVUs) are excluded from EcoDesign labelling. Our calculation software Energy Optimizer reports whether the chosen NRVU unit fulfills the EcoDesign requirements or not for the intended project.

General information

Air volume flow @ 100 Pa: 50–1300 m³/h
Pressure difference: 25–100 Pa
Leakage external: < 5% (test pressure 300Pa)
Leakage internal: < 5% (test pressure 300Pa)
Duct size: Ø 250 mm
Weight: 130 kg
Standard filters, 2 x bag filter: ISO ePM1 60%/ISO Coarse 80% (F7/M5)
IP class: IP44 (external control IP20)
Condense connection: ¼” internal thread
Nominal voltage: 230 V, models with electrical heater 3000 W/230 V and 4000 W/400 V.
Nominal current: Motors xx A total, electrical after heating x A

Fans

Supply and exhaust air fan type:
Supply and exhaust air motor type:
Nominal voltage:
Type of fan blade:
Nominal power:
Fan control eAir control: Stepless (supply and exhaust running separately)

Heat exchanger

Heat exchanger type: Rotating heat exchanger
Material: Aluminium
Heat exchanger surface: 92 m²
Heat exchanger dimensions: 520 x 200 (60 μ)
Heat exchanger motor: 6 W
Ventilation unit annual temperature efficiency (EN 13141-7:2010): 76,3 %
Supply air annual heat recovery efficiency* (EN 16798-3:2017): 90 %
Extract air annual heat recovery efficiency* (D5:2012): 76,2 %
* supply air +18°C, extract air +21°C, exhaust air temperature limit -7°C

Other information

Material inside cover: Steel sheet, zinc coated
Material outside cover: Steel sheet, zinc coated
Sound level in supply air duct at fan speeds 20, 40, 60, 80 and 100% LWA:
LPA, dB(A), 10 m²: sound absorption:
Standard electric after heater efficiency: 4 000 W / 3 000 W
Positioning of cooling (CG) coil: in duct

Do you need help choosing the right product?

We will gladly help you. Contact our customer service phone +358 9 4255 0305 (week days 8-16 UTC+2), e-mail: enervent@enervent.com or technical support phone +358 9 4255 0303 (week days 8-16 UTC+2), e-mail: service@enervent.com.